A standard Type A RCD can fail to trip properly on certain DC fault currents that some EV charger internal electronics can produce. AS/NZS 3000 requires either a Type B RCD, or a charger with equivalent built-in DC leakage protection (RDC-DD), on the EV charging circuit. This is a genuine safety requirement, not an upsell.
Most new EV chargers sold in Australia now include that built-in DC protection, which means a Type A RCD at the board is fine — but it has to be confirmed for your specific charger model, not assumed. See EV charger installation across Sydney or compare tethered vs untethered chargers.
Blue Link Electrical Services is a NSW licensed electrical contractor (licence 332956C), based in Marrickville, fitting EV chargers across Sydney since 2016. We check this on every install — call 0421 772 661.
Detects standard AC residual current and pulsating DC current. This is the common RCD type fitted in most Australian homes and is fine for ordinary power points, lighting and most appliances.
Everything a Type A detects, plus smooth DC residual current — the kind that some EV charger power electronics (and some solar inverters) can produce under a fault condition. A Type A RCD can be "blinded" by this DC current and fail to trip when it should.
An EV charger's onboard electronics convert AC to DC to charge the battery. If something fails internally, it's possible for that fault to appear as a DC leakage current that a Type A RCD can't reliably detect — meaning the circuit might not trip during a genuine fault. That's the exact scenario Type B protection (or an equivalent built-in RDC-DD device) exists to cover.
The AS/NZS 3000 wiring rules require this protection on EV charging circuits. It's typically satisfied one of two ways:
Most mainstream EV chargers sold in Australia from the last few years (Tesla Wall Connector, most Zappi, Wallbox and similar units) include built-in RDC-DD protection, which means a standard Type A RCD at the switchboard is compliant. But "most" isn't "all," and older or imported units may not — we confirm the exact model's spec before we wire it in, rather than assuming.
No — only if the charger itself doesn't have built-in DC fault protection (RDC-DD). Many modern chargers already include it, which satisfies the requirement without a separate Type B device.
Yes, noticeably more than a Type A — which is exactly why checking whether your specific charger already has built-in protection matters before assuming you need one.
Only if it's the correct type for that charger and the circuit is dedicated — EV chargers should run on their own dedicated circuit, not shared with other loads, regardless of RCD type.
Check the charger's installation manual or spec sheet for "RDC-DD" or "DC fault protection" — or send us the model and we'll confirm before the install.
Blue Link Electrical Services · NSW licence 332956C · since 2016 · fully insured · 24/7 emergency